Magnetic Lock Wiring Instructions
A.12VDC Input:
Required power 0.5Amp(Minimum)
Connect the position(+)lead from a 12VDC power source to V+
Connect the ground(-)lead from a 12VDC power source to V-
Check jumper for 12VDC operation.
B.24VDC Input:
Require power 0.25 Amp(minimum).
Connect the position(+)lead from a 24VDC power source to V+
Connect the ground(-)lead from a 24VDC power source to V-
Check jumper for 24VDC operation.
C.Contacts:
Relay dry contacts are rated 1Amp at 24VDC for safe operation,do not exceed this rating.
If you require a normally open switch,connect the wires from the system to COM and NO.
If you require a normally closed switch, connect the wires from the system to COM and NO.
Important!
If power switch is not wired between DC source voltage and magnet,it will take a longger time to de-energize the magnet simulating residual magnetism.